| Conductor | : | Fine Stranded Copper (Class 5 - Flexible Plain Copper) to VDE 0295 IEC 60228 |
| Insulation | : | Heat - resistant PVC core insulation |
| Colour | : | Green/Yellow, Blue, Black, Brown, Grey, Orange, Pink, Red, Violet, White, Green, Yellow or other colours |
| Flame propagation | : | Flame retardant test as per IEC 60332-1 |
| Operating Temp | : | -30°C max. +90°C |
| Nominal voltage | : | HO5V2-K : 300/500 V HO7V2-K : 450/750 V |
| Test voltage | : | HO5V2-K : 2000 V HO7V2-K : 2500 V |
| Insulation resistance | : | 20 MΩ x km |
| Min. bending radius | : | 4 x cable diameter |
HO5V2-K, HO7V2-K
For internal wiring of appliances as well as installation in an electrical conduit pipe either on or underneath plaster
Standard length cable packing:
Coils 100 and 200 m in carton boxes, reels
| Size in mm2 | Nos/ dia. (Nom.) | Insulation Thickness in mm ( nom.) | Outer Dia in mm (Appx.) | Max. C.R in ohm/km Copper |
| 0.5 | 16/0.200 | 0.60 | 2.10 | 39.00 |
| 0.75 | 24/0.200 | 0.60 | 2.20 | 26.00 |
| 1 | 32/0.200 | 0.60 | 2.70 | 19.50 |
| Size in mm2 | Nos/ dia. (Nom.) | Insulation Thickness in mm ( nom.) | Outer Dia in mm (Appx.) | Max. C.R in ohm/km Copper |
| 1.5 | 30/0.250 | 0.70 | 3.25 | 13.30 |
| 2.5 | 50/0.250 | 0.80 | 3.80 | 7.98 |
| 4 | 56/0.300 | 0.80 | 4.50 | 4.95 |
| 6 | 84/0.300 | 0.80 | 5.25 | 3.30 |
| 10 | 140/0.300 | 1.00 | 6.50 | 1.91 |
| 16 | 224/0.300 | 1.00 | 8.00 | 1.21 |
| 25 | 350/0.300 | 1.20 | 10.10 | 0.780 |
| 35 | 490/0.300 | 1.20 | 11.30 | 0.554 |
| 50 | 703/0.300 | 1.40 | 13.50 | 0.386 |
| 70 | 988/0.300 | 1.40 | 15.30 | 0.272 |
| 95 | 1349/0.300 | 1.60 | 18.00 | 0.206 |
| 120 | 608/0.500 | 1.60 | 19.80 | 0.161 |
| 150 | 760/0.500 | 1.80 | 22.30 | 0.129 |
| 185 | 943/0.500 | 2.00 | 23.90 | 0.106 |
| 240 | 1225/0.500 | 2.20 | 26.80 | 0.0801 |