| Conductor | : | Solid copper conductor, class 1 DIN VDE 0281,IEC 60228 |
| Insulation | : | Heat - resistant polyvinyl chloride (PVC) insulation |
| Colour | : | Green/Yellow, Blue, Black, Brown, Grey, Orange, Pink, Red, Violet, White, Green, Yellow or other colours |
| Flame propagation | : | Flame retardant test as per IEC 60332-1 |
| Operating Temp | : | -30°C to +90°C |
| Nominal voltage | : | HO5V2-U : 300/500 V HO7V2-U : 450/750 V |
| Test voltage | : | HO5V2-U : 2000 V HO7V2-U : 2500 V |
| Insulation resistance | : | 20 MΩ x km |
| Min. bending radius | : | 4 x cable diameter |
HO5V2-U, HO7V2-U
For internal wiring of appliances as well as installation in an electrical conduit pipe either on or underneath plaster
Standard length cable packing:
Coils 100 and 200 m in carton boxes, reels
| Size in mm2 | Nos/ dia. (Nom.) | Insulation Thickness in mm ( nom.) | Outer Dia in mm (Appx.) | Max. C.R in ohm/km Copper |
| 0.5 | 1/0.80 | 0.60 | 2.10 | 36.00 |
| 0.75 | 1/0.97 | 0.60 | 2.20 | 24.50 |
| 1 | 1/1.13 | 0.60 | 2.60 | 18.10 |
| Size in mm2 | Nos/ dia. (Nom.) | Insulation Thickness in mm ( nom.) | Outer Dia in mm (Appx.) | Max. C.R in ohm/km Copper |
| 1.5 | 1/1.38 | 0.70 | 3.00 | 12.10 |
| 2.5 | 1/1.78 | 0.80 | 3.60 | 7.41 |
| 4 | 1/2.24 | 0.80 | 4.10 | 4.61 |
| 6 | 1/2.78 | 0.80 | 4.70 | 3.08 |
| 10 | 1/3.57 | 1.00 | 5.80 | 1.83 |